The DT-TELE-SHDSL Surge Protector was designed to meet the special requirements of SHDSL data transmission. It is specifically designed to provide Lightning, RFI, ESD and transient surge protection for maximum data security with minimum signal attenuation.

Surge protection for SHDSL systems

Reliable telecommunications are indispensable in today's industry. The sensitive systems used in these cases work with high frequencies at low signal levels and are networked over a wide area. Surge voltages here quickly lead to largescale failures and, in the worst-case scenario, data loss. The SHDSL Surge Protector takes the form of an adapter that can be easily installed between incoming telecommunications cables and a modem. The pluggable connection ensures fast and flexible installation and only needs to be grounded by way of the black cable or DIN rail base.

Attachment plug with surge protection for two SHDSL telecommunications interfaces (ports). Connection: RJ45 (RJ12/RJ11) and plug-in screw terminal block (COMBICON). Alternatively, can be snapped onto a DIN rail.

DT-TELE-SHDS Technical Specifications

Ambient Conditions

Ambient temperature (operation)

-40°C ... 85°C

Ambient temperature (storage/transport)

-40°C ... 85°C

Degree of protection

IP20

Protective circuit

IEC test classification

  • B2
  • C1
  • C2
  • C3
  • D1

Maximum continuous voltage UC

185 V DC

Rated current

≤ 380 mA (25°C)

Operating effective current IC at UC

≤ 6 µA

Residual current IPE

≤ 4 µA

Nominal discharge current In (8/20) µs (Core-Core)

≤ 5 kA

Nominal discharge current In (8/20) µs (core-earth)

≤ 5 kA

Total discharge current Itotal (8/20) µs

10 kA

Nominal pulse current Ian (10/700) µs (Core-Core)

150 A

Nominal pulse current Ian (10/700) µs (Core-Earth)

150 A

Voltage protection level Up (core-core)

  • 250 V (B2 - 100 A)
  • ≤ 250 V (C1 - 500 A)
  • ≤ 410 V (C2 - 5 kA)

Voltage protection level Up (core-ground)

  • ≤ 580 V (B2 - 100 A)
  • ≤ 580 V (C1 - 500 A)

Response time tA (core-core)

≤ 100 ns

Response time tA (core-earth)

≤ 100 ns

Input attenuation aE, sym.

  • typ. 0.3 dB (≤ 2,8 MHz / 100 Ω)
  • typ. 3 dB (≤ 25 MHz / 100 Ω)

Cut-off frequency fg (3 dB), sym. in 100 Ohm system

25 MHz

Capacity (core-core)

55 pF

Capacity (core-earth)

7 pF

Surge protection fault message

None

Impulse durability (conductor-conductor)

C1 - 1 kV/500 A

Impulse durability (conductor-ground)

  • B2 - 4 kV/100 A
  • C1 - 1 kV/500 A
  • C2 - 10 kV/5 kA

VDE requirement class

  • B2
  • C1
  • C2
  • C3
  • D1

Maximum continuous voltage UC

130 V AC

Pulse discharge current Iimp (10/350) µs

2.5 kA (Number of pulses category D1)

Nominal pulse current Ian (10/1000) µs (Core-Core)

100 A

Nominal pulse current Ian (10/1000) µs (Core-Earth)

100 A

Voltage protection level Up (core-core)

≤ 250 V (C3 - 100 A)

Voltage protection level Up (core-ground)

  • ≤ 790 V (C2 - 5 kA)
  • ≤ 300 V (C3 - 100 A)

Resistance in series

3.3 Ω 20 %

Impulse durability (conductor-conductor)

  • C2 - 10 kV/5 kA
  • B2 - 4 kV/100 A

Impulse durability (conductor-ground)

D1 - 1 kA

Standards and Regulations

Standards / specifications

  • IEC 61643-21 2002
  • IEC 61643-21

General

Housing material

Zinc die-cast

Color

silver/black

Mounting type

Connection-specific attachment plug and DIN rail, 35 mm

Design

Attachment plug for DIN rail mounting

Number of positions

4

Direction of action

Line-Line & Line-Ground/Shield

Standards for cearances and creepage distances

  • IEC 60664-1
  • VDE 0110-1

Connection, equipotential bonding

Connection method

Cable connection/DIN rail

Connection data

Connection method

RJ45/COMBICON

Connection method IN

RJ45 socket

Connection method OUT

RJ45 socket

Connection method IN

MC 1,5/4

Connection method OUT

MC 1,5/4

Connection technology

Screw connection

Screw thread

M2

Tightening torque

0.22 Nm

Stripping length

7 mm

Conductor cross section flexible

0.14 mm² ... 1.5 mm²

Conductor cross section solid

0.14 mm² ... 1.5 mm²

Conductor cross section AWG

28 ... 16

Dimensions

Height

103 mm

Width

25 mm

Depth

63 mm

SURGE PROTECTOR

Environmental Product Compliance

Reach and RoHS Compliant

Approvals

  • UL Listed
  • EAC

Commercial data

Packing unit

1

Weight per piece

320.0 g

Country of origin

Germany

Circuit Diagram

Circuit Diagram

Protection Against Surge Voltage

Digital telecommunications systems (DSL) are safely protected against surge voltage by SHDSL Surge Protectors. Due to the high bandwidth of the surge protectors, the transmission signal is not influenced. Use is possible up to DSL 16000. All signal wires and the ground conductor must be connected to the surge protector according to the connection scheme. Any DIN rail should be grounded.

Protection Against Surge Voltage

Product Image

Product Description

Power Cord & Part No.

DT-TELE-SHDSL Surge Protector | Order Details | Perle

DT-TELE-SHDSL Surge Protector - surge protection device for two SHDSL telecommunications interfaces (ports). Connection: RJ45 (RJ12/RJ11) and plug-in screw terminal block

Hi!

Have a Question? Chat with a live Product Specialist!

Have a Question?

We can provide more information about our products or arrange for a price quotation.


email-icon Send an Email
contactus-icon Send an Email callus-icon Call Us
×

Send us an Email