UNO-PS/1AC/48DC/60W Single-Phase DIN Rail Power Supply
48V Industrial Power Supply, AC to DC Converter
- 48V DC Output Voltage
- 1.25 Amps
- 60 Watts
- Single phase AC Input
- Input Voltage Range: 85 ... 264 V AC
The UNO-PS/1AC/48DC/60W Industrial Power Supply is a rugged AC to DC Converter built to meet the high stability and efficiency expectations of industrial, machine automation and process control environments. This Switching (switch mode) Power Supply ensures a regulated output voltage even in the event of voltage fluctuations in the power supply network. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, the UNO Industrial Power Supply is designed to meet the needs of your industrial application.
With the NEC designation as a Class 2 Power Supply, all regulations address the wiring requirements (wire size and insulation, wire derating factors, overcurrent protection limits and methods of wiring installation) between the output of the supply and the input of the load are met by the UNO-PS/AC. The output voltage and power delivery capabilities of this Class 2 power supply will lower the risk of fire initiation and electrical shocks, which allows for lower cost wiring methods to be employed when installing an electrical system in a building.
Industrial operating temperature of -25°C to +70°C
Equipment found in traffic management, oil and gas pipelines, weather tracking, industrial and outdoor applications must function in temperatures that cannot be supported by a commercial power supplies. With an operating temperature of -25°C to +70°C, the UNO-PS/1AC/48DC/60W Industrial Power Supply is ideal for use with equipment subjected to harsh environments and severe temperatures.
High efficiency up to 89% and no load power consumption <0.3W
Compared with other products on the market, the UNO Industrial Power Supply provides excellent energy savings. With a very low no load power consumption (below .3 W) and 89% efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making this a very ECO friendly power supply.
Ideal application environments for an UNO-PS/1AC/48DC/60W DIN Rail Power Supply
- automated production process
- industrial control, automation, assembly, and test equipment
- building control, security and surveillance, and climate control systems.
- power countless industrial automation devices such as sensors, controllers and valves
Other reasons to choose the UNO-PS/1AC/48DC/60W Industrial Power Supply
- 35 mm wide DIN Rail mount narrow housing
- Voltage Isolation input/output: 4 kV AC
- LED indicator for voltage out failure: If the output voltage is below the operational range, the LED turns off.
- Protections: Short-circuit, Overload, Over voltage, Over-temperature
- High MTBF (Mean Time Between Failure) values ensure maximum availability
- IEC Protection Class II Power Supply
Environmental Product Compliance
REACH SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
General
Net weight
0.21 kg
Efficiency
- typ. 89 % (120 V AC)
- typ. 89 % (230 V AC)
Insulation voltage input/output
- 4 kV AC (type test)
- 3 kV AC (routine test)
Protection class
II (in closed control cabinet)
Degree of protection
IP20
MTBF (IEC 61709, SN 29500)
1138502 Hours (40°C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: 0 mm horizontally, 30 mm vertically
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise immunity
EN 61000-6-2:2005
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 2)
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3 V/m
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
- EN 61000-6-3
- EN 61000-4-6
Frequency range
10 kHz ... 80 MHz
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-11
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Safety of transformers
EN 61558-2-16
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Limitation of mains harmonic currents
EN 61000-3-2
UL approvals
- UL/C-UL listed UL 508
- UL/C-UL Recognized UL 60950-1
- UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4A (Hazardous Location)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
- < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
- 15 Hz ... 150 Hz, 2.3g, 90 min.
Approval - requirement of the semiconductor industry with regard to mains voltage dips
EN 61000-4-11
Information technology equipment - safety (CB scheme)
CB Scheme
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
8 mm
Screw thread
M3
Output data
Nominal output voltage
48 V DC ±1 %
Nominal output current (IN)
1.25 A (-25°C ... 55°C)
Derating
55°C ... 70°C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback resistance
< 60 V DC
Protection against surge voltage on the output
≤ 60 V DC
Control deviation
- < 1 % (change in load, static 10 % ... 90 %)
- < 2 % (Dynamic load change 10 % ... 90 %, 10 Hz)
- < 0.1 % (change in input voltage ±10 %)
Residual ripple
< 35 mVPP (with nominal values)
Output power
60 W
Typical response time
< 1 s
Maximum power dissipation in no-load condition
< 0.4 W
Power loss nominal load max.
< 7 W
Dimensions
Width
35 mm
Height
90 mm
Depth
84 mm
Weight per piece
243.0 GRM
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC
Current consumption
- 1.3 A (100 V AC)
- 0.6 A (240 V AC)
Nominal power consumption
134.7 VA
Inrush surge current
< 30 A (typical)
Mains buffering
- typ. 20 ms (120 V AC)
- typ. 90 ms (230 V AC)
Input fuse
2 A (slow-blow, internal)
Choice of suitable circuit breakers
6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi)
0.5
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Connection data, onput
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
8 mm
Screw thread
M3
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25°C ... 70°C (> 55°C derating, 2.5 %/K)
Ambient temperature (storage/transport)
-40°C ... 85°C
Max. permissible relative humidity (operation)
≤ 95 % (at 25°C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Approvals
- UL Recognized
- cUL Recognized
- cUL Listed
- IECEE CB Scheme
- UL Listed
Application Diagrams
UNO-PS/1AC Industrial Power Supply Block Diagram
Click on a part number for ordering information
Product Image
Product Description
Power Cord & Part No.
UNO-PS/1AC/48DC/60W Power Supply - UNO power supply for DIN rail mounting, input: 1-phase, output: 48 V DC/60 W