UNO-PS/350-900DC/24DC/60W DIN Rail Power Supply
Regulated DC to DC Converter
- 24V DC Output Voltage
- 2.5 Amps
- 60 Watts
- Input Voltage Range: 300 V DC ... 1000 V DC
If you need to efficiently produce a regulated 24 V DC output voltage from a source that may or may not be well controlled to a load that may or may not be constant, the UNO-PS/350-900DC/24DC/60W Power Supply is for you. This DC to DC converter enables direct connection to string voltages of up to 1000 V DC. This means the Combiner Box is supplied directly from the photovoltaic panel and additional installation costs are not incurred. In another expansion stage, the signal line can be replaced by a wireless connection. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, the UNO Industrial DC to DC Converter is designed to meet the needs of your industrial application.
Industrial operating temperature of -25°C to +70°C
Equipment found in traffic management, oil and gas pipelines, weather tracking, industrial and outdoor applications must function in temperatures that cannot be supported by a commercial power supplies. With an operating temperature of -25°C to +70°C, and reliable device start-up at -40°C, the UNO Industrial Power Supply is ideal for use with equipment subjected to harsh environments and severe temperatures.
High efficiency over 90% and low no load power consumption
Compared with other products on the market, the UNO Industrial Power Supply provides excellent energy savings. With a very low no load power consumption and over 90% efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making this a very ECO friendly power supply.
Ideal application environments for an UNO DC to DC converter
- Supply your control cabinet directly from the photovoltaic system to save on installation costs and increase system efficiency.
- Where an AC connection is not available and direct field installation needed.
Other reasons to choose the UNO DC to DC Converter
- UL 1741 certification simplifies approval of the overall system
- LED function monitoring simplifies start-up
- Minimal space required in the control box
- High Voltage Isolation input/output value of 8 kV
- Protections: Short-circuit, Overload, Over voltage, Over-temperature
- High MTBF (Mean Time Between Failure) values ensue maximum system availability
Environmental Product Compliance
REACH SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
General
Net weight
0.3 kg
Efficiency
> 90 %
Insulation voltage input/output
- 8 kV DC (type test)
- 3 kV DC (routine test)
Protection class
II
Degree of protection
IP20
MTBF (IEC 61709, SN 29500)
> 1160000 Hours (40°C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: 0 mm horizontally, 30 mm vertically
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise immunity
EN 61000-6-2:2005
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 3)
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3 V/m
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
- EN 61000-6-3
- EN 61000-4-6
Frequency range
10 kHz ... 80 MHz
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-11
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard
IEC 62109-1
Standard - Electrical safety
IEC 62109-1
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Limitation of mains harmonic currents
EN 61000-3-2
UL approvals
UL 1741
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
- < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
- 15 Hz ... 150 Hz, 2.3g, 90 min.
Approval - requirement of the semiconductor industry with regard to mains voltage dips
EN 61000-4-11
Information technology equipment - safety (CB scheme)
CB Scheme
Overvoltage category (IEC 62109-1)
II
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
8 mm
Screw thread
M3
Output data
Nominal output voltage
24 V DC ±1 %
Nominal output current (IN)
2.5 A (-25°C ... 55°C)
Derating
55°C ... 70°C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
No
Feedback resistance
< 35 V DC
Protection against surge voltage on the output
≤ 35 V DC
Control deviation
- < 1 % (change in load, static 10 % ... 90 %)
- < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
- < 0.1 % (change in input voltage ±10 %)
Residual ripple
< 20 mVPP (with nominal values)
Output power
60 W
Typical response time
< 1 s
Maximum power dissipation in no-load condition
< 0.5 W
Power loss nominal load max.
< 6.5 W
Dimensions
Width
55 mm
Height
90 mm
Depth
84 mm
Weight per piece
316.9 GRM
Input data
Nominal input voltage range
350 V DC ... 900 V DC
Input voltage range
300 V DC ... 1000 V DC
Dielectric strength maximum
≤ 1050 V DC
Current consumption
- 0.19 A (350 V DC)
- 0.07 A (1000 V DC)
Inrush surge current
< 1 A (typical)
Choice of suitable circuit breakers
1 A (Characteristic gPV or comparable)
Connection data, onput
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
8 mm
Screw thread
M3
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25°C ... 70°C (> 55°C derating, 2.5 %/K)
Ambient temperature (start-up type tested)
-40°C
Ambient temperature (storage/transport)
-40°C ... 85°C
Max. permissible relative humidity (operation)
≤ 95 % (at 25°C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Approvals
- cULus Recognized
- EAC
- UL Recognized
- cUL Recognized
- IECEE CB Scheme
Application Diagrams
UNO-PS/350-900DC/24DC/60W Industrial Power Supply Block Diagram
Click on a part number for ordering information
Product Image
Product Description
Power Cord & Part No.
UNO-PS/350-900DC/24DC/60W Power Supply - UNO DC/DC converter with wide range input, for DIN rail mounting, input: 350 ... 900 V DC, output: 24 V DC/60 W