TRIO-PS-2G/1AC/48DC/5 Single-Phase DIN Rail Power Supply
48V Industrial Power Supply for Regulated AC/DC or DC/DC Conversion
- 48 DC Output Voltage
- 5 Amps
- 240 Watts
- Single phase AC or DC Input
- Input Voltage Range: 85 ... 264 V AC and 99 ... 275 V DC
The TRIO-PS-2G/1AC/48DC/5 Industrial Power Supply is a rugged AC to DC and DC to DC Converter built to meet the high stability and efficiency expectations of industrial, machine automation and process control environments. This Switching (switch mode) Power Supply ensures a regulated output voltage even in the event of voltage fluctuations in the power supply network. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, TRIO Industrial Power Supply is designed to meet the needs of your industrial application.
150% Dynamic Power Boost
The dynamic boost provides additional power for starting difficult loads. By supplying up to 150% of the nominal current for 5 seconds, the TRIO-PS-2G/1AC/48DC/5 power supply starts difficult loads reliably.
36 to 55 V DC Adjustable Output Voltage Range
Using the rotary potentiometer on the front face of the TRIO-PS-2G/1AC/48DC/5 power supply, the output voltage can be optimally adjusted to meet specific application environment requirements. For example, you can easily adjust to compensate for a voltage drop caused by a long cable length.
Industrial operating temperature of -25°C to +70°C with reliable device start-up at -40°C
Equipment found in traffic management, oil and gas pipelines, weather tracking, industrial and outdoor applications must function in temperatures that cannot be supported by a commercial power supplies. With an operating temperature of -25°C to +70°C and reliable device start-up at -40°C, the TRIO-PS-2G/1AC/48DC/5 Industrial Power Supply is ideal for use with equipment subjected to harsh environments and severe temperatures.
High efficiency and low no load power consumption
Compared with other products on the market, the TRIO Industrial Power Supply provides excellent energy savings. With a very low no load power consumption and high efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making these very ECO friendly power supplies.
Easy & efficient installation
The tool-free Push-in connection will save time and make installation quick and easy. And, the DIN Rail mount narrow housing will save space in the control cabinet.
Ideal application environments for a TRIO-PS-2G DIN Rail Power Supply
- machine building
- automated production process
- industrial control, automation, assembly, and test equipment
- building control, security and surveillance, and climate control systems.
- power countless industrial automation devices such as sensors, controllers and valves
Other reasons to choose this TRIO-PS-2G Industrial Power Supply
- Contact signal output and LED indicator for voltage out failure: If the output voltage is below the operational range, the LED turns off and the contact opens.
- Vibration resistance up to 4 kg
- Shock resistance up to 30g
- Voltage Isolation input/output: 3 kV AC
- Protections: Short-circuit, Overload, Over voltage, Over-temperature
- High MTBF (Mean Time Between Failure) values of more than 1 million hours at +40°C ensure maximum availability
Environmental Product Compliance
REACH SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
General
Net weight
0.9 kg
Efficiency
- typ. 90.5 % (120 V AC)
- typ. 91 % (230 V AC)
Insulation voltage input/output
- 3 kV AC (type test)
- 1.5 kV AC (routine test)
Protection class
I (in closed control cabinet)
Degree of protection
IP20
MTBF (IEC 61709, SN 29500)
- > 2000000 Hours 25°C
- > 1200000 Hours (40°C)
- > 620000 Hours 60°C
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: horizontally 0 mm (≤ 40°C) 10 mm (≤ 70°C), vertically 50 mm
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise emission
EN 55011 (EN 55022)
Noise immunity
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 2)
Standards/regulations
EN 61000-4-3
Frequency range
1.4 GHz ... 2 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3 V/m (Test Level 2)
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
- EN 61000-6-3
- EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Conducted noise emission
EN 55016 EN 61000-6-4 (Class A)
Standards/regulations
EN 61000-4-11
Low Voltage Directive
Conformance with Low Voltage Directive 2014/35/EC
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Limitation of mains harmonic currents
EN 61000-3-2
UL approvals
- UL Listed UL 508
- UL/C-UL Recognized UL 60950-1
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
- DNV GL CG-0339 / Class B
- 2 Hz - 100 Hz resonance search, 90 min. in resonance,
2 Hz - 25 Hz, ±1.6 mm amplitude,
25 Hz - 100 Hz, 4g acceleration
Rail applications
EN 50121-4
Overvoltage category
(EN 60950-1)
II
Overvoltage category
(EN 62477-1)
III
Connection data, input
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
10 mm
Output data
Nominal output voltage
48 V DC ±1 %
Setting range of the output voltage (USet)
36 V DC ... 55 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (IN)
5 A
Dynamic Boost (IDyn.Boost)
7.5 A (5 s)
Derating
> 60°C ... 70°C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback resistance
≤ 60 V DC
Protection against surge voltage on the output
≤ 60 V DC
Control deviation
- < 1 % (change in load, static 10 % ... 90 %)
- < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
- < 0.1 % (change in input voltage ±10 %)
Residual ripple
< 20 mVPP (with nominal values)
Output power
240 W
Peak switching voltages nominal load
< 15 mVPP
Maximum power dissipation in no-load condition
- typ. 4 W (120 V AC)
- typ. 4.1 W (230 V AC)
Power loss nominal load max.
- typ. 24.5 W (120 V AC)
- typ. 20.1 W (230 V AC)
Short-circuit current
< 7 A DC (Permanent)
Connection data for signaling
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
16
Stripping length
8 mm
Dimensions
Width
42 mm
Height
130 mm
Depth
160 mm
Weight per piece
1120.0 GRM
Input data
Nominal input voltage range
- 100 V AC ... 240 V AC
- 110 V DC ... 250 V DC
Input voltage range
- 100 V AC ... 240 V AC -15 % ... +10 %
- 110 V DC ... 250 V DC ±10 %
Dielectric strength maximum
≤ 300 V AC 15 s
AC frequency range
50 Hz ... 60 Hz ±10 %
Discharge current to PE
< 3.5 mA
Current consumption
- 2.9 A (100 V AC)
- 2.3 A (120 V AC)
- 1.2 A (230 V AC)
- 1.2 A (240 V AC)
Nominal power consumption
285.7 VA
Mains buffering
- typ. 15 ms (120 V AC)
- typ. 15 ms (230 V AC)
Input fuse
6.3 A (internal (device protection))
Choice of suitable circuit breakers
6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi)
0.91
Connection data, onput
Connection method
Push-in connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
8 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25°C ... 70°C (> 60°C derating, 2.5 %/K)
Ambient temperature (start-up type tested)
-40°C
Ambient temperature (storage/transport)
-40°C ... 85°C
Max. permissible relative humidity (operation)
≤ 95 % (at 25°C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Installation height
≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Approvals
- cULus Listed
- cULus Recognized
- EAC
- UL Recognized
- cUL Recognized
- cUL Listed
- UL Listed
Application Diagrams
TRIO-PS-2G/1AC Industrial Power Supply Block Diagram
Click on a part number for ordering information
Product Image
Product Description
Power Cord & Part No.
TRIO-PS-2G/1AC/48DC/5 Power Supply - TRIO supply for DIN rail mounting, input: 1-phase, output: 48 V DC / 5 A