QUINT4-SYS-PS/1AC/24DC/2.5/SC Power Supply
Single-Phase DIN Rail 24V Industrial Power Supply

- Output voltage 24 VDC
- Adjustable output voltage ranges: 24 to 27 VDC
- 2.5 A
- 60 Watts
- Single phase AC or DC input
- Input voltage range: 100 to 240 VAC
- Support for output power via TBUS adapter
- IECEx/ATEX/Hazloc
The QUINT4-PS/1AC/12DC/15 Industrial Power Supply is rugged AC to DC and DC to DC Converter built to meet the high stability and efficiency expectations of industrial, machine automation and process control environments. It is capable of delivering power using a DIN rail bus distributor (TBUS adapter) and it can be directly latched onto the DIN rail. Featuring a protective coating, IECEx, ATEX, and HazLoc approvals, this power supply can be used in the harshest environments.
The OVP (overvoltage protection) of <30 VDC protects your system against voltage increases. In the event of an error, the output is switched off to protect the loads against overvoltage. The output circuit is decoupled by a MOSFET.
QUINT Power Supplies are exceptionally small yet offer superior system availability in the sub 100 W power range.
- Static boost of up to 125% (PN) for a sustained period
- Dynamic boost of up to 200% (PN) for 5 s
- Space-saving Slim design
- Preventive Function monitoring through adjustable signaling of power thresholds or output voltage
- Durable– Efficiency up to 94%– Low power dissipation
Input voltage range
- 100 V AC ... 240 V AC -15 % ... +10 %
- 110 V DC ... 250 V DC -20 % ... +40 %
Mains buffering
- typ. 31 ms (120 V AC)
- typ. 31 ms (230 V AC)
Nominal output voltage (UN)
24 V DC
Setting range of the output voltage (USet)
24 V DC ... 27 V DC
Nominal output current (IN)
2.5 A
Static Boost (IIStat.Boost)
3.125 A (≤ 40°C)
Dynamic Boost (IDyn.Boost)
4 A (≤ 60 °C (on ≤ 5 s/off ≥ 5 s))
Output power (PN)
60W
Output power (PStat.Boost)
75W
Output power (PDyn.Boost)
90W
Electric strength of the insulation
- Type test ( IEC/EN 61010-1 ): 4 kV AC
- Production test: 3 kV AC
- Field test: 2 kV AC
Efficiency
- typ. 93 % (120 V AC)
- typ. 94 % (230 V AC)
Residual ripple
< 40 mVPP
MTBF @230vAC (IEC 61709, SN 29500)
> 2000000 h (25 °C)
> 1161000 h (40 °C)> 514000 h (60 °C)
Operating temperature
- -25 °C ... 70 °C
- -40°C (startup type tested)
- >60 °C Derating: 2,5 %/K
Vibration (operation)
5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Degree of protection
IP20
Dimensions W/H/D
40 mm / 99 mm / 114 mm
Net weight
0.25 kg
Standards and Regulations
Rail applications
- EN 50121-3-2
- EN 50121-4
- EN 50121-5
- IEC 62236-3-2
- IEC 62236-4
- IEC 62236-5
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard – Safety extra-low voltage
- IEC 61010-1 (SELV)
- IEC 61010-2-201 (PELV)
Standard - Safe isolation
- IEC 61558-2-16
- IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use
- IEC 61010-1
- IEC 61010-2-201 (SELV)
Standard - Safety of transformers
EN 61558-2-16
Overvoltage category
- EN 61010-1 (II (≤ 5000 m))
- EN 62477-1 (III (≤ 2000 m))
UL Approvals
- ANSI/UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
- UL 61010-1
- UL 61010-2-201
- UL 1310 Class 2 Power Units
ATEX
- UL 21 ATEX 2597X
- Ex II 3 G Ex ec nC IIC T4 Gc
IECEx
- IECEx ULD 21.0023X
- Ex ec nC IIC T4 Gc
UKEX
UL21UKEX2208X
SIQ
CB scheme (IEC 61010-1, IEC 61010-2-201)
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Interference emission
Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise immunity
Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply)
EMC requirements for power supply
- IEC 61850-3 (G,H)
- EN 61000-6-5 (switching devices)
Conducted noise emission
- EN 55016
- EN 61000-6-3 (Class B)
Noise emission
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Harmonic currents
- EN 61000-3-2
- EN 61000-3-2 (Class A)
- Frequency Range: 0 kHz ... 2 kHz
Flicker
- EN 61000-3-3
- Frequency Range: 0 kHz ... 2 kHz
Electrostatic discharge
- Contact discharge: 8 kV (Test Level 4)
- Discharge in air: 15 kV (Test Level 4)
Electromagnetic HF field
EN 61000-4-3
Fast transients (burst)
EN 61000-4-4
Surge voltage load (surge)
EN 61000-4-5
Part Number: 29046148
QUINT4-SYS-PS/1AC/24DC/2.5/SC Power Supply - QUINT Power Supply with DIN rail mounting, input: 1-phase, output: 24 V DC / 2.5 A

Contact Perle Sales
Purchase from our E-Store

Find A Distributor