QUINT4-PS/1AC/24DC/3.8/PT Single-Phase DIN Rail Power Supply
24V Industrial Power Supply for Regulated AC/DC or DC/DC Conversion
- 24 V DC Output Voltage
- Adjustable Output Voltage Ranges: 24 to 28 V DC
- 3.8 Amps
- 91.2 Watts
- Single phase AC or DC Input
- Input Voltage Range: 85 ... 264 V AC and 88 ... 350 V DC
The QUINT4-PS/1AC/24DC/3.8/PT Industrial Power Supply is rugged AC to DC and DC to DC Converter built to meet the high stability and efficiency expectations of industrial, machine automation and process control environments. It also feature the unique combination of preventive function monitoring and power reserve in an incredibly compact size. This Switching (switch mode) Power Supply ensures a regulated output voltage even in the event of voltage fluctuations in the power supply network. During parallel operation, and when connected to different phases, loads are reliably supplied even in the event of problems with the input voltage. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, this QUINT Industrial Power Supply is designed to meet the need of your industrial application.
POWER BOOST: reliably start difficult loads
A high degree of flexibility is required to configure, optimize and expand large systems. To optimally adapt a system or machine to your requirements, a power reserve in the power supply unit is crucial. The QUINT4-PS/1AC/24DC/3.8/PT supplies up to 50% additional current without a voltage drop. This is useful when it is not possible to predict which loads will be switched on at the same time or high switch-on currents of capacitive loads have to be absorbed without voltage dips. You can use the dynamic boost to supply 185% of the nominal current for 5 seconds when starting up heavy loads.
Preventive function monitoring reports critical operating states before they occur
With the QUINT4-PS/1AC/24DC/3.8/PT Industrial Power Supply, the output voltage and output current are constantly monitored. Preventive function monitoring visualizes critical operating states and indicates them locally and remotely to the controller as follows:
- Via LED
- Via floating relay contact
- Via active switching output
High efficiency and low no load power consumption
Compared with other products on the market, this QUINT Industrial Power Supply provides excellent energy savings. With a very low no load power consumption and high efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making these very ECO friendly power supplies.
- Tripping circuit breakers: The circuit breaker is typically tripped by the high SFB current within 3 to 5 ms. As a result, any voltage dips for loads connected in parallel are avoided.
- Tripping a fuse: Fuses are tripped by melting the predetermined breaking point inside the fuse capsule. The tripping characteristic of the fuse is described by the melting integral (I²t). A high current is crucial in order to achieve a very short tripping time.
Ideal application environments for the QUINT4-PS/1AC/24DC/3.8/PT DIN Rail Power Supply
- Shipbuilding
- machine building
- automated production process
- industrial control, automation, assembly, and test equipment
- building control, security and surveillance, and climate control systems.
- power countless industrial automation devices such as sensors, controllers and valves
Other reasons to choose the QUINT4-PS/1AC/24DC/3.8/PT Industrial Power Supply
- Shipbuilding Approvals
- Adjustable Output Voltage Ranges: the output voltage can be optimally adjusted to meet specific application environment requirements, such as compensating for a voltage drop caused by a long cable length.
- Robust input side: high noise immunity, integrated gas-filled surge arrester (up to 6 kV), and ≥ 20 ms mains failure buffer time
- Configurable signaling of DC OK or selectable power thresholds
- Space savings in the control box, thanks to a narrow, slim-line design
- Voltage Isolation input/output: 4 kV AC
- Protections: Short-circuit, Overload, Over voltage, Over-temperature
- To ensure maximum availability all models have high MTBF (Mean Time Between Failure) values.
Industrial Class 2 Power Supply
With the NEC designation as a Class 2 Power Supply, all regulations address the wiring requirements (wire size and insulation, wire derating factors, overcurrent protection limits and methods of wiring installation) between the output of the supply and the input of the load are met by this QUINT. The output voltage and power delivery capabilities of this Class 2 power supply will lower the risk of fire initiation and electrical shocks, which allows for lower cost wiring methods to be employed when installing an electrical system in a building.
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 25;
General
Net weight
0.296 kg
Efficiency
- typ. 92.8 % (120 V AC)
- typ. 93.7 % (230 V AC)
Insulation voltage input/output
- 4 kV AC (type test)
- 3 kV AC (routine test)
Protection class
II
Degree of protection
IP20
MTBF (IEC 61709, SN 29500)
> 1272000 Hours (25°C)
> 690000 Hours (40°C)> 271000 Hours (60°C)
Assembly instructions
DIN rail mounting
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 2)
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3 V/m (Test Level 2)
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Conducted noise emission
EN 55016 EN 61000-6-4 (Class A)
Standards/regulations
- EN 61000-4-8
- EN 61000-4-11
- EN 61000-4-9
- EN 61000-4-12
- EN 61000-4-16
- EN 61000-4-18
Standard - Safety of transformers
EN 61558-2-16
Standard - Electrical safety
IEC 61010-2-201 (SELV)
Standard - power supply devices for low voltage with DC output
EN 61204-3
Standard – Safety extra-low voltage
- IEC 61010-1 (SELV)
- IEC 61010-2-201 (PELV)
Standard - Safe isolation
- IEC 61558-2-16
- IEC 61010-2-201
Standard – Limitation of mains harmonic currents
EN 61000-3-2
UL approvals
- UL Listed UL 61010-1
- UL Listed UL 61010-2-201
- UL 1310 Class 2 Power Units
- ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6)
Overvoltage category
(EN 61010-1)
II
Overvoltage category
(EN 62477-1)
III (≤ 2000 m)
Connection data, input
Connection method
Push-in technology
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Output data
Nominal output voltage
24 V DC
Setting range of the output voltage (USet)
24 V DC ... 28 V DC (constant capacity)
Nominal output current (IN)
3.8 A
Dynamic Boost (IDyn.Boost)
7 A (≤ 60°C (5 s))
Derating
> 60°C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Feedback resistance
≤ 35 V DC
Protection against surge voltage on the output
≤ 32 V DC
Control deviation
- < 0.5 % (Static load change 10 % ... 90 %)
- < 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
- < 0.2 % (change in input voltage ±10 %)
Residual ripple
< 45 mVPP (with nominal values)
Output power
90 W
Typical response time
500 ms
Maximum power dissipation in no-load condition
- < 1 W (120 V AC)
- < 1 W (230 V AC)
Power loss nominal load max.
- < 7 W (120 V AC)
- < 6 W (230 V AC)
Connection data for signaling
Connection method
Push-in technology
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Dimensions
Width
45 mm
Height
106 mm
Depth
90 mm
Weight per piece
380.0 GRM
Input data
Input voltage range
- 100 V AC ... 240 V AC -15 % ... +10 %
- 110 V DC ... 250 V DC -20 % ... +40 %
Dielectric strength maximum
300 V AC 30 s
Discharge current to PE
< 0.25 mA (264 V AC, 60 Hz)
Current consumption
- 1 A (100 V AC)
- 0.83 A (120 V AC)
- 0.46 A (230 V AC)
- 0.44 A (240 V AC)
Nominal power consumption
104 VA
Inrush surge current
typ. 13 A (at 25°C)
Mains buffering
- typ. 35 ms (120 V AC)
- typ. 35 ms (230 V AC)
Input fuse
3.15 A (slow-blow, internal)
Choice of suitable circuit breakers
6 A ... 16 A (Characteristic B, C, D, K or comparable)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Connection data for signaling
Connection method
Push-in technology
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
10 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25°C ... 70°C (> 60°C Derating: 2.5 %/K)
Ambient temperature (start-up type tested)
-40°C
Ambient temperature (storage/transport)
-40°C ... 85°C
Max. permissible relative humidity (operation)
≤ 95 % (at 25°C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Installation height
≤ 5000 m (> 2000 m, observe derating)
Approvals
- cULus Listed
- DNV GL
- EAC
- cUL Listed
- IECEE CB Scheme
- UL Listed
Application Diagrams
QUINT-1-Phase Industrial Power Supply Block Diagram
Schematic diagram
Input current vs output current
Power factor diagram
Efficiency diagram
Click on a part number for ordering information
Product Image
Product Description
Power Cord & Part No.
QUINT4-PS/1AC/24DC/3.8/PT Power Supply - QUINT power supply with Push-in technology, DIN rail mounting, input: 1-phase, output: 24 V DC / 3.8 A