QUINT-PS/3AC/24DC/20/CO – 3-Phase DIN Rail Power Supply
For extreme ambient conditions
- 24 V DC Output Voltage
- 20 Amps
- 480 Watts
- 3-phase AC input Voltage Range: 320 to 575 V AC
- 2-phase AC or DC input Voltage Range: 360 to 575 V AC and 450 to 800 V DC
The QUINT-PS/3AC/24DC/20/CO 3-Phase Power Supply is specifically designed to operate in hazardous industrial locations and extreme ambient conditions. The PCB coating protects against dust, corrosive gases, and 100% humidity as well as failures caused by corrosion-related creepage currents and electrochemical migration. In addition, the components are protected within a wide temperature range of -40°C to 70°C. This makes the QUINT-PS/3AC/CO Industrial Power Supply is ideal for use with equipment subjected to harsh environments and severe temperatures.
The QUINT-PS/3AC/24DC/20/CO is a 3-Phase 24V DC Power Supply built to meet the high stability and efficiency expectations of industrial, machine automation and process control environments. It features the unique combination of preventive function monitoring and power reserve in an incredibly compact size. This Switching (switch mode) Power Supply ensures a regulated output voltage even in the event of voltage fluctuations in the power supply network. During parallel operation, and when connected to different phases, loads are reliably supplied even in the event of problems with the input voltage. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, this QUINT Industrial Power Supply is designed to meet the needs of your industrial application.
18 to 29.5 V DC Adjustable Output Voltage Range
Using the rotary potentiometer on the front face of the QUINT power supply, the output voltage can be optimally adjusted to meet specific application environment requirements. For example, you can easily adjust to compensate for a voltage drop caused by a long cable length.
POWER BOOST: reliably start difficult loads
A high degree of flexibility is required to configure, optimize and expand large systems. To optimally adapt a system or machine to your requirements, a power reserve in the power supply unit is crucial. The QUINT supplies up to 50% additional current without a voltage drop. This is useful when it is not possible to predict which loads will be switched on at the same time or high switch-on currents of capacitive loads have to be absorbed without voltage dips.
Preventive function monitoring reports critical operating states before they occur
With a QUINT Industrial Power Supply, the output voltage and output current are constantly monitored. Preventive function monitoring visualizes critical operating states and indicates them locally and remotely to the controller as follows:
- Via LED
- Via floating relay contact
- Via active switching output
High efficiency and low no load power consumption
Compared with other products on the market, the QUINT Industrial Power Supply provides excellent energy savings. With a very low no load power consumption and high efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making these very ECO friendly power supplies.
SFB (Selective Fuse Breaking) Technology
SFB Technology can be used to quickly and reliably trip miniature circuit breakers and fuses connected on the secondary side. In the event of a short circuit on the secondary side, the QUINT supplies up to 6 times the nominal current for 15 ms. Faulty current paths are switched off selectively, the fault is located, and important system parts remain in operation. Loads that are connected in parallel are still supplied with energy ensuring continued operation of these system parts.
- Tripping circuit breakers: The circuit breaker is typically tripped by the high SFB current within 3 to 5 ms. As a result, any voltage dips for loads connected in parallel are avoided.
- Tripping a fuse: Fuses are tripped by melting the predetermined breaking point inside the fuse capsule. The tripping characteristic of the fuse is described by the melting integral (I²t). A high current is crucial in order to achieve a very short tripping time.
Ideal application environments for a QUINT DIN Rail Power Supply
- Shipbuilding
- Railways
- Drive motors and other devices
- Machine building
- Automated production process
- Industrial control, automation, assembly, and test equipment
- Building control, security and surveillance, and climate control systems.
- Power countless industrial automation devices such as sensors, controllers and valves
Other reasons to choose a QUINT Industrial Power Supply
- High MTBF (Mean Time Between Failure) values
- Robust input side: high noise immunity, integrated gas-filled surge arrester (up to 6 kV), and ≥ 20 ms mains failure buffer time
- Narrow, slim-line design saves space in the control box
- Voltage Isolation input/output: 4 kV AC
- Protections: Short-circuit, Overload, Over voltage, Over-temperature
- Shipbuilding Approvals
- Railway Approvals
Environmental Product Compliance
REACH SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
General
Net weight
1.5 kg
Efficiency
> 93 % (at 400 V AC and nominal values)
Insulation voltage input/output
- 4 kV AC (type test)
- 2 kV AC (routine test)
Insulation voltage input / PE
- 3.5 kV AC (type test)
- 2 kV AC (routine test)
Insulation voltage output / PE
500 V DC (routine test)
Protection class
I
Degree of protection
IP20
MTBF (IEC 61709, SN 29500)
- > 900000 h (25°C)
- > 534000 h (40°C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components,
50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm
vertically bottom
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Connection in acc. with standard
CSA
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 2)
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3 V/m (Test Level 2)
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
- EN 61000-6-3
- EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
EN 50178
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Equipment safety
BG (design tested)
Shipbuilding approval
DNV GL (EMC A), ABS, LR, RINA, NK, BV
UL approvals
- UL/C-UL listed UL 508
- UL/C-UL Recognized UL 60950-1 (3-wire + PE, star net)
- UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
- < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
- 15 Hz ... 150 Hz, 2.3g, 90 min.
Approval - requirement of the semiconductor industry with regard to mains voltage dips
SEMI F47-0706 Compliance Certificate
Information technology equipment - safety (CB scheme)
CB Scheme
Rail applications
EN 50121-4
Noxious gas test
ISA-S71.04-1985 G3 Harsh Group A
Overvoltage category
(EN 62477-1)
III
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
18
Conductor cross section AWG max.
10
Stripping length
7 mm
Screw thread
M4
Output data
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
20 A (-25°C ... 60°C, UOUT = 24 V DC)
POWER BOOST (IBoost)
26 A (-25°C ... 40°C permanent, UOUT = 24 V DC)
Selective Fuse Breaking (ISFB)
120 A (12 ms)
Derating
60°C ... 70°C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Feedback resistance
max. 32 V DC
Protection against surge voltage on the output
< 32 V DC
Control deviation
- < 1 % (change in load, static 10 % ... 90 %)
- < 3 % (change in load, dynamic 10 % ... 90 %)
- < 0.1 % (change in input voltage ±10 %)
Residual ripple
< 40 mVPP (with nominal values)
Output power
480 W
Typical response time
< 0.16 s
Peak switching voltages nominal load
< 40 mVPP (at nominal values, 20 MHz)
Maximum power dissipation in no-load condition
11 W
Power loss nominal load max.
40 W
Connection data for signaling
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
18
Conductor cross section AWG max.
10
Screw thread
M4
Dimensions
Width
69 mm
Height
130 mm
Depth
125 mm
Width with alternative assembly
125 mm
Height with alternative assembly
130 mm
Depth with alternative assembly
72 mm
Weight per piece
1873.0 GRM
Input data
Nominal input voltage range
3x 400 V AC ... 500 V AC
Input voltage range
- 3x 320 V AC ... 575 V AC
- 2x 360 V AC ... 575 V AC
- 450 V DC ... 800 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Discharge current to PE
< 3.5 mA
Current consumption
- 3x 1.6 A (400 V AC)
- 3x 1.3 A (500 V AC)
- 0.9 A (600 V DC)
Nominal power consumption
783 VA
Inrush surge current
< 20 A (typical)
Current consumption
- typ. 28 ms (400 V AC)
- typ. 43 ms (500 V AC)
Choice of suitable circuit breakers
6 A ... 16 A (AC: Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor, gas-filled surge arrester
Connection data for signaling
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
12
Conductor cross section AWG max.
10
Stripping length
7 mm
Screw thread
M4
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40°C ... 70°C (> 60°C Derating: 2.5 %/K)
Ambient temperature (start-up type tested)
-40°C
Ambient temperature (storage/transport)
-40°C ... 85°C
Max. permissible relative humidity (operation)
100 % (at 25°C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Installation height
5000 m
Approvals
- DNV GL
- cULus Recognized
- EAC
- UL Recognized
- CSA
- Bauartgeprüft
- cUL Recognized
- cUL Listed
- IECEE CB Scheme
- UL Listed
Application Diagrams
QUINT-PS/3AC/24DC/20/CO Industrial Power Supply Block Diagram
Click on a part number for ordering information
Product Image
Product Description
Power Cord & Part No.
QUINT-PS/3AC/24DC/20/CO Power Supply - QUINT power supply for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, with protective coating, input: 3-phase, output: 24 V DC/20 A